Applies to: NOD-AX Series Readers
Summary
This article provides instructions for installing Wavelynx Ethos readers on either mullion or single-gang mounting surfaces.
Mounting the Reader
To mount the NOD-AX Series Reader:
- Position the metal wall plate over the mullion or single-gang electrical box.
- Secure the wall plate using the provided #6 screws.
- Connect the reader’s terminal block or wiring harness to the control panel, following the Specifications Table at the end of this article.
- Align the reader with the installed wall plate.
- Slide the reader into position, ensuring proper alignment and engagement with the backplate.
- Secure the bottom of the reader using either a #4-40 Phillips screw or the included Pin-in-Torx screw (depending on your desired tamper resistance level).
Specifications Table
| Wire Color | Function | Description |
| 🔴 Red | Power In | Provides power to the reader |
| ⚫ Black | Ground | Electrical ground connection |
| 🟢 Green | Data 0 (Wiegand) / RS485 A (OSDP) | Transmits Data 0 (Wiegand) or RS485 A signal (OSDP) |
| ⚪ White | Data 1 (Wiegand) / RS485 B (OSDP) | Transmits Data 1 (Wiegand) or RS485 B signal (OSDP) |
| 🟤 Brown * | Control (Tamper Output) | Used for tamper detection (if applicable) |
| 🔵 Blue * | Green LED Control | Controls green LED indicator |
| 🟡 Yellow * | Buzzer Control | Controls buzzer sound (if applicable) |
| 🟠 Orange | Red LED Control | Controls red LED indicator |
NOTE: Wires marked with an asterisk (*) may be optional or only required
in specific configurations.